Flame detector FD 201x feed

The flame detector system FD 201x / FD 202x is designed for operation at continuous operating heat treating units. The universal use and also the easy integration in the main system are specific for this monitoring unit. It also complies with the requirement of the European Standard EN 298 and EN 230. Fail safe ionisation monitoring is working with common or separate spark and monitoring electrodes. UV-monitoring is working in intermitted mode. Mixing mode UV and ionisation is possible with FD2012 / 2022. Operation is visualized by 2/3 LED’s. Signal contacts are given potential free, measuring points for the flame signal on the front plate.

FD 2011

  • approved for EN 298 / EN 230
  • 19” pcb 100x160mm, 6TE/3HE
  • fail-safe Ionisation
  • Ionisation with common or separated electrode
  • connector by DIN 41612, model F z+d, 32p
  • integrated power supply 115/230VAC 50/60Hz +10/-15%
  • 1-channel

FD 2012

  • See FD 2011, but 2-channel

FD 2011

Monitoring of ionization with common spark- and supervising electrode

FD 2011, FD 2012

Monitoring of ionization with separate spark- and supervising electrode

FD 2011, FD 2012

Monitoring with UV-tube

 Protection for the contacts:

  • AC:     RC-combination or Varistor (metalloxyd)
  • DC:     diodes (Ublock > 5 x Uvalve)

Maximum length of cable:

Ionization monitoring: max. 75m, ionization cable separate from power, cable SIHF 1 x 1,5mm².
UV-monitoring: max. 50m, cable Ölflex YSLY-JZ 3 x 1,5mm²..